Walk-in cooler troubleshooting, symptom by symptom
By Vimal Bhaya, Founder and Lead Systems Architect · Last reviewed 4 October 2026
This is a continuation of How walk-ins work, and how they fail, a 4-part tutorial. You are on part 2 of 4.
A walk-in cooler that will not hold temperature is the most reported problem, and the condensing unit is the first place to look.
Check that it is running, that its fan is turning, and that you can see through its coil. Those three checks need no tools.
If the box is above 41°F (5°C), or 4°C (39°F) in Ontario, move the food to another cold box now and call a technician.
Seven symptoms cover most walk-in cooler problems
Find what you are seeing, then jump to its section. Each section lists its reasons most reported first: most reported in the public threads we read and in the technicians' answers to them. That is not the same as how often each fault happens in the field, which nobody publishes.
Symptoms 6 and 7 had no thread of their own in our research. Their reasons come from our symptom matrix and manufacturers' manuals instead.
| # | What you see | What it usually is | Parts to suspect | Can you check it yourself? | How urgent |
|---|---|---|---|---|---|
| 1 | Lost capacity, or too much load | Expansion valve, condenser, refrigerant, evaporator fans | Partly. Look at the condensing unit and the fans | Today if above 41°F (5°C) | |
| 2 | Warm, wet air getting in | Door gasket, closer, strip curtain | Yes. Look at the gasket and let the door close itself | This week | |
| 3 | The coil never gets a chance to clear | Thermostat, evaporator fans, refrigerant | Partly. Check the setting and the fans | Within a day. A warm box is next | |
| 4 | Told to run too cold, or cannot stop | Thermostat and controller, compressor contactor | Partly. Check the setting | Today. Frozen produce is lost | |
| 5 | Too much load, or wrong pressure settings | Pressure switches, refrigerant, condenser, door | Partly. Time a few cycles | This week | |
| 6 | The drain is not carrying the water away | Drain line, trap and pan, condensate pump | Yes. Look in the pan and follow the drain line | This week. Today if it drips on food | |
| 7 | Overheating, or a failing starting part | Condenser, compressor and its starting parts, contactor | Partly. Check the breaker once and look at the condenser | Today: a stopped unit is not cooling |
Here is a list of seven things you can check to assess your walk-in's health
None of these needs a tool or an open panel.
- The condensing unit. Listen at the outdoor or back-room cabinet. Should be: running and resting in turn. Silence with a warm box points to the next check.
- The switch and the breaker. Look at the disconnect switch beside the unit and at the breaker panel. Should be: the switch on and the breaker in. Tell the technician what you find. Do not keep resetting a breaker that trips again.
- The fans in the box. Should be: turning. On most coolers they run all the time.
- The condenser coil. Look through the guard. Do not reach in. Should be: clean enough to see through. A coil you cannot see through cannot get rid of heat.
- The door. Open it a few inches and let go. Should be: it swings shut and seals all the way round by itself.
- The thermostat setting. Should be: above 32°F (0°C), commonly about 35°F (2°C), with the food at 41°F (5°C) or colder, or 4°C (39°F) in Ontario.
- The coil's air. Should be: nothing stacked against the unit or in front of its fans.
Leave gauges, refrigerant and anything inside an electrical panel to a technician. Never chip or pick ice off the coil. The tubes are thin, and one hole turns an ice problem into a refrigerant leak.
1. A walk-in cooler that runs warm usually has a starved coil, a dirty condenser, a refrigerant leak or a stopped fan
The box creeps above its setting and stays there, or recovers slowly after every delivery. Staff notice warm drinks first.
"Walk in cooler not holding at temperature"
r/healthinspector, thread title
Reason 1: An expansion valve that feeds too little starves the coil
- Parts: expansion valve.
- What happens: The valve meters refrigerant into the coil through a fine screen. If debris blocks the screen, or the valve is set or driven to feed too little, the box cannot pull down. A starved coil is the cause named in two of the threads we read on this symptom.
- The proof: for the technician: readings that look like a leak, but no leak found.
- Check: a technician's job.
- What to do next: Probe the food and move anything above 41°F (5°C) to other cold storage. Book a technician today, and say the box will not pull down.
Reason 2: A dirty condenser or a hot spot round the unit cuts capacity on hot afternoons
- Parts: condenser coil and fan.
- What happens: If the condenser cannot shed heat, the whole loop slows down. An outdoor unit suffers in the sun. An indoor unit suffers in a hot kitchen, breathing grease, flour and its own exhaust.
- The proof: warm on hot afternoons or during service, fine overnight, and a coil you cannot see through.
- Check: look at the coil and fan through the guard, and feel the air round an indoor unit.
- What to do next: If the coil is furred, switch the unit off at its disconnect and book a cleaning this week. If the air round an indoor unit is hot, clear space round it.
Reason 3: A refrigerant leak makes the cooler lose ground week by week
- Parts: refrigerant leaks and charge.
- What happens: Less refrigerant moves less heat. The box holds on cool days, then slips a little further every week. The coil may start to ice.
- The proof: a slow slide over weeks, and a unit that runs longer and longer.
- Check: a technician's job. Tell them how long the slide has been going on.
- What to do next: Book a technician this week to find and fix the leak. Probe the food each day until then, and move anything above 41°F (5°C).
Reason 4: A stopped evaporator fan warms the box within hours
- Parts: evaporator fans.
- What happens: With a fan out, less air crosses the coil. The box warms unevenly, and the coil can ice.
- The proof: one fan still while the others turn.
- Check: from the floor, look at each fan.
- What to do next: If a fan is still, call a technician today and keep the door shut. Probe the food near that fan first.
Reason 5: Too much load is not a broken part
- Parts: none. The load is the problem, not a part.
- What happens: A door left open, a pallet of warm product, or a system too small for the box from the start all look like a fault. Nothing is broken, so there is no part to replace.
- The proof: warm after deliveries or a busy service, recovering when the box is left alone. A system that was always marginal shows it in its first hot week.
- Check: note when it happens: after deliveries, during service, or all the time.
- What to do next: If it recovers once the box is left alone, spread deliveries out and load food already cold. If it never catches up, ask a technician whether the system is big enough.
Less often: an outdoor unit that has lost its winter controls: head-pressure control and crankcase heater, which warms the box on cold nights rather than hot afternoons. The walk-in freezer page explains the pattern under warm on cold nights.
When several boxes on one site run warm at once, look for what they share: one condensing unit, one electrical feed, or one rack. That points away from any single box.
Before you call, check these five things
- Is the condensing unit running, with its fan turning?
- Can you see through the condenser coil?
- Are all the evaporator fans turning?
- Is the coil icing?
- Is it worse in the afternoon, after deliveries, or all the time?
- When to call a technician: today if the box is above 41°F (5°C), or 4°C (39°F) in Ontario. A stopped fan or a tripped unit can warm the box within hours. A slow slide over weeks can wait for a booked visit, but book it.
- What to tell them: the box temperature, since when, what time of day it is worst, which fans are turning, and whether the coil is icing.
2. Condensation inside a walk-in cooler means warm, wet air is getting in
Water beads on the ceiling and walls, drips onto product, or a frost line forms along the door. The door may stick, swing open, or not quite close.
"Help? This regularly occurs in the walk in cooler at my bar"
r/refrigeration, thread title
Reason 1: A gasket gone hard, torn or loose lets air in all day
- Parts: door gasket, closer, strip curtain and door heaters.
- What happens: The gasket is the seal round the door. In time it hardens, tears or pulls away from the door. Every gap pulls in warm, damp kitchen air.
- The proof: wet or frosty patches along one side of the door, and gaps or tears in the gasket.
- Check: look all the way round the gasket, and at the sweep along the bottom.
- What to do next: If the gasket is hard, torn or loose, order the maker's replacement this week. Until then, keep the door shut and wipe the water off.
Reason 2: A door out of line, or a failed closer, leaves a gap
- Parts: door closer and hinges.
- What happens: US federal rules require walk-in doors to have closers that pull them firmly shut from within an inch of closed. A closer that has failed, or a door that has dropped on its hinges, leaves the door resting just open.
- The proof: the door does not swing shut and seal by itself, or it rubs the frame.
- Check: open it a few inches and let go.
- What to do next: If the door does not swing shut, have the hinge or closer fixed this week. Until then, ask staff to push it fully shut every time.
Reason 3: A missing strip curtain, or a propped door, lets the kitchen in
- Parts: strip curtain.
- What happens: Federal rules also require strip curtains, spring-hinged doors or another way to limit air coming in while the door is open. Curtains get taken down because they are in the way, and doors get propped during deliveries.
- The proof: condensation that is worst after deliveries and busy service.
- Check: check the curtain is up and whole, and watch how the door is used during a delivery.
- What to do next: Put the strip curtain back, or replace it if torn, and stop the door being propped. The condensation should ease within a day or two.
Reason 4: Air leaking through panel joints wets the box from the outside in
- Parts: wall panels and pipe holes, which have no part page.
- What happens: The walls are panels locked together. A joint that has opened, or a hole cut for a pipe and never sealed, lets humid air into the wall and the box.
- The proof: wet or frosty lines along panel joints or round pipe holes, away from the door.
- Check: look along the joints and round every pipe that enters the box.
- What to do next: Show a technician or the panel installer the wet lines, and ask them to seal the joints and pipe holes.
Before you call, check these four things
- Is the gasket whole all the way round?
- Does the door close and seal on its own?
- Is the strip curtain up and whole?
- Is the wet patch by the door, or along a panel joint?
- When to call a technician: this week. A door or gasket is often a maintenance or door-company job rather than a refrigeration call.
- What to tell them: where the water forms, whether the door closes by itself, and whether it is worse after deliveries.
3. Ice on a walk-in cooler's coil means it is set too cold, never switches off, or has a stopped fan or low refrigerant
A cooler's coil clears its own frost every time the cooling switches off. So if ice is building, something is stopping that from happening.
"Commercial cooler frozen up"
r/hvacadvice, thread title
Reason 1: A thermostat set too cold leaves the coil no chance to clear
- Parts: thermostat, controller and pressure switches.
- What happens: Off-cycle defrost only works while the box air is above freezing. Emerson's refrigeration manual uses it for rooms of 35°F (2°C) or warmer. Set the box colder, and the air the fans blow over the coil cannot melt the frost.
- The proof: the setting is at or near freezing, and the box reads that cold too.
- Check: check the setting on the thermostat or controller.
- What to do next: If the setting is at or near freezing, raise it to what your manual says, and watch whether the ice shrinks over the next day. If it does not, call a technician to melt it safely.
Reason 2: A cooler that never switches off never defrosts
- Parts: none, usually. The load, or a system too small for the box.
- What happens: If the compressor runs nonstop, there is no rest for the fans to clear the coil. The cause is usually load: a door left open, warm product, or a system too small for the box.
- The proof: the compressor runs for hours without a break, and the ice grows during busy days.
- Check: listen for the compressor stopping. See runs all the time.
- What to do next: If it never rests, follow the runs-all-the-time section to find out why. Once it rests, the coil should clear between cycles.
Reason 3: A stopped evaporator fan lets the coil freeze in place
- Parts: evaporator fans.
- What happens: The fans both carry the cold away and, during each rest, carry the box's warmer air in to melt the frost. With a fan stopped, that part of the coil freezes solid.
- The proof: ice in front of one fan, and that fan not turning.
- Check: from the floor, look at each fan.
- What to do next: If a fan is still and iced, call a technician today. Never chip the ice round it.
Reason 4: Too little refrigerant makes part of the coil too cold
- Parts: refrigerant leaks and charge.
- What happens: With too little refrigerant, the part of the coil that does get it runs colder than it should, and frosts heavily while the rest stays bare.
- The proof: ice on one end or one section of the coil, and a box running warmer than usual.
- Check: a technician's job. It needs gauges.
- What to do next: Book a technician this week, and say only part of the coil ices. Probe the food meanwhile.
Less often: product stacked against the coil, so air cannot get through. Or, on coolers with a defrost timer, off cycles set too short to clear the coil.
Before you call, check these five things
- What is the thermostat set to?
- Does the compressor ever stop?
- Are all the fans turning?
- Is the ice all over, or in front of one fan?
- Is product blocking the unit?
- When to call a technician: within a day. An iced coil moves less heat, so a warm box is usually next. Do not chip the ice. A technician can melt it safely and find out why.
- What to tell them: the setting, whether the compressor ever stops, where the ice is, and which fans are turning.
4. A walk-in cooler that freezes the food is usually set too cold, or a stuck valve or contactor keeps it running
Lettuce turns glassy, milk has ice in it, and the thermometer reads below freezing. Sometimes it happens slowly. In one thread the box held 36°F (2°C) for weeks, then dropped to 18°F (-8°C).
"Walk in cooler. Too cold"
r/KitchenConfidential, thread title
Reason 1: The thermostat setting or its sensor is the most reported cause
- Parts: thermostat, controller and pressure switches.
- What happens: Someone turned the dial, the controller lost its settings, or its sensor has failed, come loose or moved to a warmer spot, so it keeps asking for cold. The machine is doing what it is told.
- The proof: the setting is lower than it should be, or the controller shows a normal reading while a separate thermometer in the box reads much colder.
- Check: check the setting, and compare the controller's reading with a thermometer near the food.
- What to do next: If the setting is too low, set it back to your manual's figure. If the controller disagrees with your thermometer, book a technician to check the sensor.
Reason 2: A valve that sticks open keeps feeding the coil
- Parts: liquid line valve.
- What happens: On most split systems the thermostat stops the cooling by closing a valve on the liquid pipe. If that valve sticks open, refrigerant keeps flowing after the box is cold enough.
- The proof: the box keeps cooling past its setting, often after weeks of behaving normally.
- Check: a technician's job.
- What to do next: Book a technician within a day. Meanwhile, move the most delicate food, like lettuce, away from the unit.
Reason 3: A contactor stuck closed means the compressor never stops
- Parts: compressor, contactor and starting parts.
- What happens: The contactor is the heavy switch that turns the compressor on and off. On systems where the thermostat switches the compressor directly, contacts that weld shut keep it running whatever the thermostat says.
- The proof: the compressor runs nonstop, and turning the thermostat up makes no difference.
- Check: a technician's job. Do not open the panel.
- What to do next: Call a technician today, and do not open the panel. If food is freezing fast, switch the unit off at its disconnect until they arrive, and probe the box.
Reason 4: Product in the cold air stream freezes in a healthy box
- Parts: none. Where the product sits is the problem.
- What happens: The air leaving the coil is much colder than the box. Food stacked right in front of the fans can freeze even when the box itself is fine.
- The proof: only the product near the unit is freezing.
- Check: move it and see if the problem stops.
- What to do next: If moving it stops the freezing, keep that product out of the air stream from now on.
Before you call, check these four things
- What is the thermostat set to, and has anyone changed it?
- Does a separate thermometer agree with the controller?
- Does the compressor ever stop?
- Is only the product near the fans freezing?
- When to call a technician: today if the box is below freezing. Frozen produce and dairy are usually lost, and a compressor that never stops is wearing itself out.
- What to tell them: the setting, the actual box temperature, whether the compressor stops, and when it started.
5. A walk-in cooler that never stops, or clicks on and off, usually has a dirty condenser, a bad seal, low refrigerant or a pressure setting wrong
A healthy cooler runs, rests, and runs again. One that runs for hours without a break is losing a fight with its load. One that clicks on and off every few minutes is being stopped by something before it finishes.
"Brewery walk-in cooler underperforming when cold"
r/refrigeration, thread title
Reason 1: Pressure control settings can make a cooler short cycle
- Parts: thermostat, controller and pressure switches.
- What happens: Many systems start and stop the compressor on a low-pressure switch. If its cut-in and cut-out settings are wrong, the compressor stops and starts in quick bursts. That is the answer in the thread above.
- The proof: the compressor clicks on and off every few minutes, while the box struggles to hold.
- Check: time a few cycles with your phone, and tell the technician.
- What to do next: Give the technician your cycle timings, and ask them to check the pressure control settings this week.
Reason 2: Low refrigerant trips the low-pressure switch over and over
- Parts: refrigerant leaks and charge.
- What happens: With too little refrigerant, pressure falls fast once the compressor starts. The low-pressure switch stops it, pressure recovers, and it starts again.
- The proof: short cycles that began gradually, and a box that has been getting warmer.
- Check: a technician's job.
- What to do next: Book a technician this week to find the leak. Short cycling wears the compressor, so do not leave it for months.
Reason 3: A dirty condenser or a bad door seal makes it run for hours
- Parts: condenser coil and fan; door gasket, closer, strip curtain and door heaters.
- What happens: A condenser that cannot shed heat, or a door that lets warm air in all day, means the compressor never catches up.
- The proof: the compressor almost never rests, and the box is barely holding.
- Check: look at the condenser coil and the door gasket.
- What to do next: If the condenser is furred, switch the unit off at its disconnect and book a cleaning. If the gasket leaks, see the wet walls section.
Less often: a system too big for the box, which cools it so fast that it short cycles. That one is built in, not broken.
Before you call, check these four things
- Does the compressor run for hours, or click on and off every few minutes?
- Time three cycles: how long on, how long off?
- Is the condenser coil clean?
- Does the door seal?
- When to call a technician: this week. Short cycling wears a compressor out, and a cooler that never rests will soon ice its coil.
- What to tell them: how long it runs and rests, when it started, and whether the box is holding.
6. Water on the floor under a walk-in cooler unit means the drain is not carrying it away
A cooler makes water all day. Every time the cooling rests, the coil's light frost melts and drips into a pan under the unit, and a drain line carries it out of the box. Water on the floor under the unit, or dripping off its front edge, means that water is not getting away. If the water is on the walls and ceiling instead, see symptom 2.
Reason 1: A blocked pan or drain line makes the water spill over
- Parts: drain pan and drain line. A cooler's drain has no heater.
- What happens: Dust, slime and bits of food and packaging collect in the pan and the line. The pan fills and spills over its edge.
- The proof: standing water in the pan, and drips from the edge of the unit.
- Check: look into the pan with a torch from a step ladder, without opening any panel. Heatcraft's unit cooler manual says to clean the pan regularly with warm soapy water.
- What to do next: If the pan holds water, ask maintenance or a technician to clear the drain this week. Mop up meanwhile, and put a sign out.
Reason 2: A drain line without enough fall holds water
- Parts: drain line.
- What happens: The line has to run downhill all the way. Heatcraft's manual asks for a fall of at least 1/4 inch per foot. A line that sags, or was run level, holds water, and the pan backs up behind it.
- The proof: a pan that empties slowly, and a line that dips between its supports.
- Check: follow the line from the unit to where it ends, and look for dips.
- What to do next: If the line sags, ask a technician to re-support it with a steady fall. Mop up and put a sign out until then.
Reason 3: A missing or dried-out trap lets air up the drain
- Parts: drain trap.
- What happens: A trap is a U-bend that holds a little water in the line, so air, smells and insects cannot come up it. Without one, or with one that has dried out, air pulled up the line by the fans can stop the pan from emptying.
- The proof: a pan that empties when the fans stop and fills while they run, or a smell from the drain.
- Check: look for a U-bend in the line where it leaves the box.
- What to do next: If there is no trap, or it is dry, ask a technician to fit one or refill it.
Reason 4: A failed condensate pump leaves the water nowhere to go
- Parts: condensate pump, which has no part page.
- What happens: Where there is no floor drain nearby, the water runs to a small pump that lifts it to one. If the pump stops, its tank fills and the line backs up.
- The proof: a full pump tank, and a pump that does not run when the tank fills.
- Check: check it is plugged in, and listen for it running.
- What to do next: If it is unplugged, plug it back in. If it is plugged in and silent with a full tank, ask a technician to replace it today, and mop up meanwhile.
Before you call, check these four things
- Is there water standing in the pan under the unit?
- Is it dripping from the unit, or forming on the walls and ceiling?
- Does the drain line run downhill all the way, through a U-bend?
- If there is a condensate pump, is it running?
- When to call a technician: this week, or today if water is dripping onto food or spreading across the floor, where people can slip. Mop it up, and put a tray under the drip in the meantime.
- What to tell them: where the water is, whether the pan is full, where the drain line ends, and whether there is a pump.
7. A walk-in cooler unit that trips, hums or will not start usually has a dirty condenser, a failing start part or an electrical fault
The condensing unit stops. It starts again by itself, stays off until someone resets it, or hums without starting. While it is off, nothing is cooling the box. The hot-day version of this is set out in more detail under trips on hot days on the freezer page.
Reason 1: A dirty condenser or a dead condenser fan trips the high-pressure switch
- Parts: condenser coil and fan; thermostat, controller and pressure switches.
- What happens: If the condenser cannot shed heat, pressure climbs until a safety switch stops the compressor. Some of these switches reset themselves. Others stay off until a person resets them. Heat waves, and indoor units in hot kitchens, make it worse.
- The proof: trips in the afternoon heat or during service, a coil you cannot see through, or a fan that sits still while the compressor runs.
- Check: look at the coil and fan through the guard, and feel the air round an indoor unit.
- What to do next: Switch the unit off at its disconnect before anyone cleans the coil, then book a cleaning. A still fan while the compressor runs needs a technician today.
Reason 2: A compressor that hums but will not start has a failing starting part
- Parts: compressor, contactor and starting parts.
- What happens: A compressor needs a hard kick to start. If a starting part has failed, the voltage is low, or the compressor itself is wearing out, it hums for a few seconds. Then a safety cut-out clicks it off, and a few minutes later it tries again.
- The proof: a hum, a click, then silence, over and over.
- Check: do not keep resetting it. Each failed start heats the motor. Tell the technician what you heard.
- What to do next: Leave it off, protect the food, and call a technician today. Tell them about the hum and the click.
Reason 3: A breaker that trips again points to an electrical fault
- Parts: contactor and wiring.
- What happens: If the breaker or fuse goes again soon after it is reset, something is drawing too much current. It could be a failed motor, a burned contactor or a wiring fault.
- The proof: a breaker that trips again within minutes or hours of a reset.
- Check: reset it once at most. If it goes again, leave it off and call.
- What to do next: Leave the breaker off and call a technician today. Move the food above 41°F (5°C) to other cold storage meanwhile.
Reason 4: Too much refrigerant, or air in the system after a repair, raises pressure
- Parts: refrigerant charge.
- What happens: Too much refrigerant, or air let in during a repair, leaves the system running at higher pressure than it should. A hot day then pushes it over the limit.
- The proof: the trips started soon after a service visit.
- Check: tell the technician when the last repair was.
- What to do next: Call the technician who did the last repair, and say the trips started after their visit.
Before you call, check these four things
- Is the breaker or the disconnect beside the unit off?
- Does the unit hum, click, or stay silent?
- Is the condenser fan turning, and can you see through the coil?
- Did it start soon after a service visit?
- When to call a technician: today. A unit that is off is not cooling, so watch the box and move the food if it passes 41°F (5°C), or 4°C (39°F) in Ontario.
- What to tell them: what you heard, whether a breaker tripped, the time of day, how hot it was outside or in the kitchen, and when the unit was last serviced.
One night, a busy cooler lost its ripple and stayed near 39°F (4°C) until morning
This is the same cooler as on how a walk-in cooler works, in a busy quick-service coffee shop in Ontario. On most nights it sits near 36°F (2°C) with a small ripple, as the cooling switches on and off about four times an hour.
On 31 March, after long door openings at midday, it did not come back. For 23 hours it never got below 38°F (3.4°C). Overnight it sat almost flat near 39°F (4°C), with no ripple at all. At about 11 AM the next day it dropped back to normal within the hour, and the next night looked ordinary again.
We have no service record for those two days, so we cannot say for certain what it was. A line that goes flat and will not come down usually means the cooling is running without catching up. The usual reasons are a coil that iced during the long openings (symptom 3), a door that did not close fully (symptom 2), or a fan that stopped (symptom 1).
Now look at what a simple alarm would have done. Set at 41°F (5°C) with a 30-minute delay, it would have gone off on 39 of the 46 days we have for this cooler, almost always from door traffic. On 31 March it would have gone off in the afternoon too, and looked like any other busy day. Overnight, when the box was actually stuck, it would have stayed silent, because 39°F is under the line. In Ontario, where the line is 4°C, the box sat right on it.
The same kind of change, building over eight days on a walk-in freezer, is on walk-in freezer troubleshooting.
This is where TemperatureWise is different: it is not just a threshold alarm
A threshold alarm asks one question: is it too warm right now? By the time a cooler crosses 41°F (5°C), a dirty condenser or a slow leak has usually been working on it for weeks.
TemperatureWise uses machine learning on the full temperature history of each box. It learns that box's own pattern: how it cycles, how fast it recovers after the door, and how it behaves on a hot afternoon. When the pattern changes, TemperatureWise tells you what has changed and where to look.
On the cooler above, the useful sign was not a number crossing a line. It was the ripple stopping, a change in that box's own pattern. On a walk-in freezer in Philadelphia, the same approach pointed the team to the evaporator side rather than just sending a number, and the technician found the fault on the first visit. The full story is on the freezer page.
It does not replace your technician. It tells you which one to call, and when, so you can sleep through the night. See how TemperatureWise works.
