Refrigerated display case troubleshooting, symptom by symptom

By Vimal Bhaya, Founder and Lead Systems Architect · Last reviewed 7 October 2026

This is a continuation of Reach-ins, prep tables, display cases and reefers, a 10-part tutorial. You are on part 8 of 10.

A display case that will not hold temperature is often losing its air curtain or overloaded past its load line before anything is broken.

Check that no product sits past the load line or on the grilles, that nothing blows across the front, and that the night curtain comes down at close. A case that reads warm only around its defrost times is usually normal: the product warms far less than the air.

If the product itself is above 41°F (5°C), or 4°C (39°F) in Ontario, move it and call your refrigeration contractor.

Six symptoms cover most display case problems

Find what you are seeing, then jump to its section. Reasons are listed in roughly the order the makers' manuals, ACHR News and our failure-mode reference put them. Nobody publishes how often each fault happens in the field.

Display case troubleshooting chart. Each symptom links to its section below.
#
What you see
What it usually is
Parts to suspect
Can you check it yourself?
How urgent
1
Overloading, a broken curtain, warm stock, or a refrigeration fault
Air curtain, night curtain, condenser, EPR valve, the rack
Partly. Look at the load line, the grilles and the neighbours
Today if the product is warm
2
Usually a normal defrost
Defrost settings, termination, drain
Yes. Compare the warm times with the schedule
Only if it does not recover
3
The air curtain is broken
Honeycomb, return grille, fans, drafts
Yes. Try the plastic bag test
This week. Today if product is warm
4
Too much wet air, or defrosts not clearing it
Store humidity, curtain, defrost, EPR valve
Partly
Within a day
5
The drain, its trap or the pan
Drain, trap, condensate pan
Partly. Look at the drain outlet
Today if people can slip
6
Humid air, or door heaters off
Anti-sweat heaters, door seals, store humidity
Partly
This week

Here is a list of six things you can check to assess a display case's health

None of these needs a tool or an open panel.

  1. The load line. Look at the line on the end panels, the honeycomb at the top and the return grille at the bottom. Should be: no product past the line, and nothing on either grille.
  2. Drafts. Should be: nothing blowing across the front. Structural Concepts asks for 10 feet (3 m) from ceiling air vents, 15 feet (4.5 m) from outside doors and 5 feet (1.5 m) from windows.
  3. The night curtain. Should be: pulled all the way down and hooked at close.
  4. The warm readings. Note the times. Should be: lined up with the defrost schedule: 1 to 6 defrosts a day by case type, most ending in 20 to 30 minutes.
  5. The cases next to it. Should be: holding. On a supermarket rack, if they are warm too, the fault is probably away from this case.
  6. On a self-contained case, the condenser. Should be: a clear grille and light through the coil. Hussmann asks for a cleaning once a month.

Leave the EPR valves, the rack, refrigerant and the electrical panels to your refrigeration contractor.

1. A display case that will not hold temperature is most often loaded past its line, or its air curtain is broken

The product reads warm, the case display reads high, or shoppers complain. Before calling, rule out the causes that are not broken parts.

Reason 1: Product stacked past the load line warms, and warms the case

Reason 2: A broken air curtain lets the store in

Reason 3: Warm stock loaded into the case never catches up

Reason 4: A night curtain left up, or torn, loses the overnight recovery

Reason 5: A dirty condenser on a self-contained case cuts its capacity

Reason 6: On a rack, a valve set wrong or a group fault warms the case

Less often: a store above the case's design conditions of 75°F (24°C) and 55% humidity. And on drinks merchandisers owned by a bottler, an energy-saving device that raises the setpoint on a schedule, which looks like a fault but is the design. Convenience store monitoring covers that one.

Before you call, check these five things

  1. Is any product past the load line or on a grille?
  2. Is the warmest product at the front and top?
  3. Was new stock loaded warm?
  4. Are the neighbouring cases warm too?
  5. Was the night curtain down overnight?

Catch it sooner next time. TemperatureWise learns each unit's own temperature pattern and tells you when it changes, and where to look. See temperature monitoring for grocery stores.

2. A display case that reads warm around its defrosts is usually normal, if it keeps to the schedule

The case display or a sensor reads in the 40s Fahrenheit a few times a day, then comes back down.

"Grocery store refrigerators around 45 degrees, is this normal"

r/foodsafety, thread title

During a defrost the coil is warmed until it reaches its end point, about 43°F to 48°F (6°C to 9°C) on medium-temperature cases in Hussmann's and Hill Phoenix's tables. An air sensor can be expected to read in the 40s Fahrenheit while that happens, though no maker publishes a normal reading. The product warms far less. Case controllers expect this, and delay or hide alarms through it: a Danfoss controller waits 90 minutes after a defrost before it will alarm.

So the question is not whether it reads warm. It is whether the warm reading comes on schedule and goes away. These are the reasons it might not:

Reason 1: A failed end-of-defrost sensor runs every defrost to its time limit

Reason 2: A reset clock puts defrosts in shopping hours

Reason 3: A blocked drain floods the coil after each defrost

Before you call, check these four things

  1. Do the warm readings line up with the defrost schedule?
  2. Does it recover before your controller's post-defrost alarm delay ends? That is 90 minutes by default on a Danfoss EKC 202, an alarm setting rather than a recovery standard.
  3. Are defrosts getting longer?
  4. Was there a power cut before the timing changed?

3. Warm top rows or a warm front mean the air curtain is broken

The back of the case is cold, but the product at the front or the top is warm. The curtain of cold air down the front has gaps, and the store's air is getting in. Drafts from air-conditioning vents are a common cause: see how a display case works.

An animated side view of an open multi-deck display case, back on the left and the open front on the right. Fans in the base push cold air up the back wall to the canopy, and a curtain of cold air falls from the honeycomb grille down the open front to the return grille, between the food and the warm store air. Then three things break it, one after another. A draft from an air conditioning vent blows across the front and bends the curtain into the case, and warm store air pours in. Product stacked past the load line pushes into the curtain's path, the curtain bulges round it and breaks, and warm air gets in below. Product stacked right up to the shelf above leaves no space under it, where makers ask for 1 to 2 inches. Then the curtain holds again.

Reason 1: Product, signs or baskets in the curtain's path break it

Reason 2: A dirty or badly fitted honeycomb scatters the air

Reason 3: A draft from a vent, a fan or a door blows the curtain away

Reason 4: An iced coil or a dead fan cannot push enough air

The plastic bag test. ACHR News describes a simple check: hold a light plastic bag at the front of the case. If the bag is drawn into the case, ACHR News says, so is the store's air. A technician can go further, with a smoke candle held at the return grille for about 30 seconds and a meter that measures the air's speed against the case's specification.

Before you call, check these four things

  1. Is anything sticking into the curtain, or on a grille?
  2. Is the honeycomb clean and seated?
  3. Is there a vent, fan or door blowing at the front?
  4. Does the bag test show a gap?

4. Weak air from the honeycomb, or frost on the product, means an iced coil from wet store air or failing defrosts

Air from the honeycomb is weak, frost shows on the product or in the case, or the case slowly warms over days.

Reason 1: Store humidity above 55% loads the coil with frost

Reason 2: A broken curtain or a night curtain left up pulls in wet air

Reason 3: Defrosts that are too few, or fail, leave frost behind

Reason 4: A pressure valve set too cold freezes the coil

Before you call, check these four things

  1. Is it humid in the store?
  2. Is the curtain whole, and the night curtain used?
  3. Are defrosts happening on schedule?
  4. Is the case colder than its neighbours?

5. Water on the floor or in a display case usually means a clogged drain, a failed trap or an overflowing pan

Each defrost makes water that has to drain away, to a floor drain or, on a self-contained case, to a pan that evaporates it.

Reason 1: A clogged drain backs up into the case

Reason 2: A trap or an evaporating pan that has failed lets it out

Reason 3: Cleaning water faster than the drain can take it

Before you call, check these four things

  1. Is the water in the case or on the floor?
  2. Is the drain outlet clear?
  3. Are the base panels in place?
  4. Is it only after cleaning, or after defrosts?

Catch it sooner next time. TemperatureWise learns each unit's own temperature pattern and tells you when it changes, and where to look. See temperature monitoring for grocery stores.

6. Glass doors that fog or sweat usually meet humid air, or their heaters are off

Shoppers cannot see the product, water runs down the glass, or frost forms on a freezer door's frame.

Reason 1: Door and frame heaters that are off or have failed

Reason 2: Store air more humid than the case was built for

Reason 3: A door that does not seal lets warm air in at the edge

Before you call, check these four things

  1. Is it one door or all of them?
  2. Is it only on humid days?
  3. Does each door close and seal on its own?
  4. Did a setting or a schedule change?

This is where TemperatureWise is different: it learns the defrosts and compares the cases

A threshold alarm on a display case goes off at every defrost, so staff learn to ignore it. The case controller avoids that by delaying its alarms after each defrost, by 90 minutes as standard on one Danfoss model. That also delays the alarm when something is really wrong.

TemperatureWise uses machine learning on the full temperature history of each case. It learns that case's own defrosts and store-hours pattern in its first week, so a normal defrost is not an alarm. When the pattern changes, such as defrosts that run longer, or a case that stops recovering, TemperatureWise tells you what has changed.

With a sensor in more than one case, it also shows when cases warm together, which points to the rack rather than the case, as grocery store monitoring explains. See how TemperatureWise works.

Every shape TemperatureWise watches for, and what each one points to, is on the shapes a failing cooler or freezer leaves in its temperature log.

Are you the refrigeration contractor? TemperatureWise can put your clients' failing boxes in your NOC days or weeks early, with the likely parts named: TemperatureWise for refrigeration contractors.

Common questions

Why is my display case not holding temperature?

Often because product is stacked past the load line, the air curtain is broken by a draft or a blocked grille, or warm stock was loaded. Rule those out first.

If the case still runs warm, the cause may be a dirty condenser on a self-contained case, or a valve or rack fault on a supermarket case. Check whether the neighbouring cases are warm too.

Why does my display case read warm during defrost?

Because the coil is being warmed to melt its frost, to about 43°F to 48°F (6°C to 9°C) on medium-temperature cases, and an air sensor can read in the 40s Fahrenheit while that happens. The product warms far less.

It is only a problem if the warm readings come off schedule, run longer than they used to, or do not recover.

Why is the top shelf of my open display case warm?

Usually because the air curtain is broken at the top, by product or signs in its path, a dirty honeycomb, or a draft from a vent, fan or door. Product stacked past the load line is warm for the same reason.

Try the plastic bag test from ACHR News: a broken curtain draws a light bag in.

Why is there ice on my display case's coil?

Because more water is reaching the coil than the defrosts can clear: store humidity above 55%, a broken air curtain, a night curtain left up, too few defrosts, or a pressure valve set too cold.

Hill Phoenix's cleaning steps turn the case off long enough to clear any frost or ice from the coil, and an iced case needs the same. Move the product first.

Why is there water on the floor in front of my display case?

Usually a clogged drain, a failed trap or evaporating pan, or missing base panels on a self-contained case. Cleaning with more water than the drain can take does it too.

Put out a sign and mop it up first: it is a slip risk on the sales floor.

Why do my glass display case doors fog up?

Usually because the door or frame heaters are off or have failed, or the store's air is more humid than the case was built for. A door that does not seal fogs along one edge.

Many glass-door cases are designed for a store at 75°F (24°C) and 55% humidity at most.

My display case evaporator fan stopped working. What should I replace?

Usually that fan's motor. A case has several fans, and on an open case they drive the air curtain, so a dead one shows as weak air along part of the honeycomb and warm product below it.

A technician replaces the motor that has stopped and checks the coil for ice, since an iced coil also weakens the air. Until then, probe along the case and move anything above 41°F (5°C) somewhere cold.

How is a smoke candle used when troubleshooting an open display case?

A technician lights one at the return grille, along the front of the case at the bottom, and watches where the smoke goes for about 30 seconds. Smoke drawn smoothly into the grille shows the air curtain is whole. Smoke that swirls or spills into the aisle shows it is broken, or a draft is hitting it.

Ask the store before lighting one, as smoke can set off a smoke detector. The plastic bag test on this page is a rougher check that needs no smoke.

Tell a normal defrost from a failing case