A short tutorial

How reach-ins, prep tables, display cases and reefers work, and how they fail

By Vimal Bhaya, Founder and Lead Systems Architect · Last reviewed 7 October 2026

Most of the refrigeration in a kitchen, a store or a fleet is not a walk-in. It is the reach-ins and undercounters on the line, the prep table under the sandwich station, the display cases on the sales floor and the reefer in the yard. Each one works on the same loop as a walk-in, and each one fails in its own way.

This is a ten-part tutorial in five pairs: the reach-in cooler, the reach-in freezer, the prep table, the display case and the reefer. In each pair, the first page explains how it works and what normal looks like, and the second goes symptom by symptom through what goes wrong, what to check yourself and when to call.

The 10 parts, in order

By the end you will know four things. How each of the five works, in plain words, and where its machine sits. The normal numbers for each, from the makers' own manuals, and what a healthy one looks like in real readings where we have them. Which symptom points to which cause, and which causes are not broken parts at all, like a prep table rated for a cooler room or a display case overloaded past its line. And what you can safely check before you call.

  1. 1. How a reach-in cooler works

    The parts and the five layouts, from bottom-mount to undercounter, the makers' normal numbers, and a real day of readings from a busy restaurant's drinks fridge: a big, steady sawtooth, about twice an hour.

    Read part 1
  2. 2. Reach-in cooler troubleshooting

    Seven symptoms, from a warm cabinet and an undercounter cooked by the line to frozen lettuce and water on the floor. Plus the night the same drinks fridge held flat near 46°F (8°C) for 15 hours: the shape of a door left ajar.

    Read part 2
  3. 3. How a reach-in freezer works

    The cooler's machine run colder, with heaters on the coil, the drain and the door. Why it heats its own coil a few times a day, and seven makers' defrost schedules side by side.

    Read part 3
  4. 4. Reach-in freezer troubleshooting

    Seven symptoms, led by an iced coil and a defrost gone wrong, a door that freezes shut and ice in the bottom of the cabinet. Each with its reasons, the proof and what to check.

    Read part 4
  5. 5. How a refrigerated prep table works

    How the cold air moves round the pans on a forced-air rail, and how a cold-wall rail differs. Why food stays cold only below the fill line, why the table is tested in an 86°F (30°C) room, and why the display is not the food's temperature.

    Read part 5
  6. 6. Prep table troubleshooting

    Ten symptoms, split by forced-air and cold-wall rails, led by warm food in the pans, which is usually the fill, the lid or the room rather than the machine. Plus nine checks, each with what it should read.

    Read part 6
  7. 7. How a refrigerated display case works

    The falling curtain of cold air that keeps an open case cold, the load line, night curtains, defrosts, and why the air can read in the 40s Fahrenheit during one while the food barely moves.

    Read part 7
  8. 8. Display case troubleshooting

    Six symptoms, from a broken air curtain and warm top shelves to ice, water on the floor and fogged doors. Plus how to tell a normal defrost from a failing case, and the plastic bag test.

    Read part 8
  9. 9. How a reefer unit works

    How a trailer unit blows air over the load and pulls it back underneath, the gaps the load must leave, continuous and start-stop modes, shore power and defrost.

    Read part 9
  10. 10. Reefer troubleshooting

    Five symptoms, from a warm load to a parked unit that never restarted, with the Thermo King and Carrier alarm codes behind them. Plus the Boxing Day no-start that TemperatureWise caught in Mississauga.

    Read part 10

How to use this

Read them in order if you are starting from scratch. That is the usual path. If you already know which piece you need, jump to it from the list above.

The five pairs stand alone. Start with the equipment that has the problem. The reach-in cooler pages cover undercounters, worktops, drawers and chef bases too, and the reach-in freezer pages build on the cooler pair.

Walk-in coolers and freezers have their own tutorial, how walk-ins work, and how they fail. A reach-in, a prep table and a display case all use the same refrigeration loop, explained step by step there.

The parts these pages name, from the compressor to the door heaters, each have their own page in walk-in refrigeration parts, with a section on how each one differs in reach-ins, prep tables, display cases and reefers. Every reason on the troubleshooting pages links to the part behind it.

Common questions

What is this tutorial?

Ten short articles on the refrigeration outside the walk-in, for the people who run it rather than repair it: the reach-in cooler and freezer, the prep table, the display case and the reefer trailer. Each has a how-it-works page and a troubleshooting page.

Every number comes from a maker's manual, a food code, a trade or government source, or real readings from equipment we monitor.

Where do undercounter refrigerators fit in?

In the reach-in cooler pair. An undercounter, worktop, refrigerated drawer or chef base is a reach-in built to sit under a counter or a cookline, and the reach-in cooler troubleshooting page has its own section on why they run warm there.

A reach-in freezer under a counter has the same problems, plus the freezer's own.

Which page should I start with?

The troubleshooting page for the equipment that has the problem, if something is wrong now. Each symptom says what to check first and when to call.

If nothing is wrong, start with the how-it-works page. Knowing what normal looks like is how you spot the change.

Do these pages show real temperature data?

Every chart on these pages comes from real readings. The reach-in cooler pair uses a month of readings from a restaurant's two-door drinks fridge, and the reefer troubleshooting page uses the published Mississauga no-start.

The reach-in freezer troubleshooting page shows a defrost failure in a real walk-in freezer, because the coil ices up the same way. None of these pages uses a made-up curve.

See what your equipment has been doing

Send us 30 days of readings from one reach-in, prep table, display case or reefer, or let us put a sensor on it, and we will show you its normal pattern and whether anything has started to change. No purchase needed.

Talk with usTemperature monitoring for restaurants

Also see temperature monitoring for grocery stores.

Vimal Bhaya, Founder and Lead Systems Architect, Renergy Technologies.
He spent about a decade designing the analog circuits inside enterprise server chips at Oracle, from high-speed data links to DDR4 memory systems. He now designs the sensors and the detection models behind TemperatureWise.
Sources

Last reviewed 7 October 2026.