The winter controls: how head-pressure control and a crankcase heater keep an outdoor unit working on freezing nights

By Vimal Bhaya, Founder and Lead Systems Architect · Last reviewed 20 October 2026

This is a continuation of Walk-in refrigeration parts, a 14-part tutorial. You are on part 13 of 14.

An outdoor condensing unit can work too well on a freezing night. Its condenser gets so cold that the pressure on the hot side, the head pressure, collapses, and too little refrigerant reaches the coil inside. The box warms even though the machine runs. Winter controls fix this by making the condenser worse at its job, on purpose: they switch its fans off, or back liquid up inside it. A crankcase heater keeps the compressor's oil warm while it is off.

When they fail, a box that is fine on a hot afternoon is warm at 6 AM after a freezing night. Write down the nights and the outdoor lows, and book a technician before the next cold spell.

On a freezing night, winter controls hold the pressure up

It sounds backwards: a freezer that is fine on a hot afternoon and warm at 6 AM after a freezing night. It comes down to head pressure:

An animated drawing of the refrigerant loop. Outside the box, the compressor squeezes the refrigerant into a hot gas and pushes it into the condenser coil, where a spinning fan blows the heat away and the gas turns to a warm liquid. The liquid flows through the wall to the expansion valve or capillary tube, where its pressure drops. Inside the box it boils in the evaporator coil as a cold mix, soaking up heat from the food and the air, which a second fan blows back out cold. The cool gas flows back out to the compressor, and the loop starts again.

Winter controls fix this by making the condenser worse at its job, on purpose. One maker's installation manual lists three parts:

  1. Fan cycling. A control switches condenser fans off as the condenser gets cold. The manual sets it to stop a fan when the condensing temperature drops to about 90°F (32°C). It says never to cycle every condenser fan on one control, and to keep each fan at least 5 minutes on and 5 off.
  2. A flooding valve, often called a head-pressure control valve. It backs liquid refrigerant up inside the condenser, so less of it can cool the gas, and holds the pressure at its setting: about 180 psi on Heatcraft's high-pressure systems. The system needs extra refrigerant to do it.
  3. A crankcase heater. A small heater on the compressor stops liquid refrigerant settling in its oil while it sits off in the cold. The manual says one is required, and asks for it to be on for 24 hours before a first start.
Two views of an outdoor condensing unit on a freezing night, animated. Top, with no winter controls: the condenser fan spins in the freezing air, the head pressure gauge reads low, and only a thin trickle of refrigerant reaches the coil inside, so the box warms. Bottom, with winter controls working: the fan has stopped and liquid is backed up in the lower part of the condenser, the pressure gauge reads normal, a full flow reaches the coil, and a small heater keeps the compressor's oil warm.

So on a cold night, a condenser fan standing still can look like a failure. It is the winter controls working, as the condenser coil and fan page explains.

Winter controls fail in three common ways

Each one shows up only when it is cold outside. The troubleshooting pages show where each sits among the other reasons for the same symptom.

Winter control faults, and the symptom each one shows up as.
What the readings show
What you see
Fault
Where it is covered
A climb in the small hours that tracks the outdoor cold
Warm overnight and early in the morning on the coldest nights, back to normal by the afternoon
Failed or missing head-pressure control
The box climbs from a unit that is not running
A compressor that struggles or will not start after a cold night
A failed crankcase heater
A climb on the coldest nights
The same night-time warming, from a unit in a room that is not heated
An indoor unit in an unheated room

Here is what failed winter controls do to the rest of the refrigeration system

A condenser that is too cold sounds harmless. It is not:

"Walk-in freezer cold weather problem"

r/refrigeration, thread title

The answer in that thread was a head-pressure control and a crankcase heater: the two parts on this page.

Failed winter controls show on the coldest nights

The pattern is easy to miss, because the box looks fine every afternoon:

Put the warm nights next to the outdoor lows, and the pattern lines up with the cold. That list is what the technician needs.

You can spot the pattern, and leave the controls to the technician

  1. Write down the nights it happened, and how cold it was outside.
  2. On a cold night, a still condenser fan is normal. It is the winter controls working.
  3. After a cold night, check the compressor starts. If it struggles or will not start, call a technician today.
  4. Check the food is still frozen after each cold night.
  5. Book a technician before the next cold spell, with your list of nights and outdoor lows.

Do not keep resetting a compressor that will not start after a cold night. Do not adjust the winter controls yourself: they are set against the refrigerant's pressures, and that is a technician's job.

Winter controls matter wherever the condenser meets the cold

Which equipment needs winter controls, and what goes wrong.
Unit
Winter controls
What goes wrong
More on this
Walk-in, outdoor or roof unit
Yes, in the outdoor cabinet
A failed head-pressure control or crankcase heater
Walk-in, indoor unit
Usually none, as long as the room is heated
An unheated room behaves like outdoors
Reach-in and prep table
None. They are built for indoor rooms: True's from 60°F to 104°F (16°C to 40°C), Beverage-Air's from 60°F to 100°F (16°C to 38°C), and Randell's prep tables from 70°F to 86°F (21°C to 30°C)
A cabinet in a cold, unheated room can run outside its range
Display case
Self-contained cases sit in the heated store. Supermarket cases share a rack whose condenser is outside
The rack's controls are the refrigeration contractor's
Reefer
The unit heats as well as cools: a fresh load in winter runs in heating mode
A stopped unit lets the load fall toward the outdoor temperature. Weak batteries and gelled diesel stop restarts

The simpler way: TemperatureWise watches for failed winter controls

Everything on this page takes time, and you have to know what to look for. TemperatureWise takes that complexity out:

It does not replace your technician. It tells you which one to call, and when.

This is one of our walk-in refrigeration parts pages. The compressor page covers the part the crankcase heater protects.

Common questions

Why does my walk-in freezer get warm on cold nights?

Usually its winter controls have failed or were never fitted. On a freezing night an outdoor condenser gets so cold that the head pressure collapses, and too little refrigerant reaches the coil inside.

Write down the nights and the outdoor lows, and book a technician before the next cold spell.

What is head pressure control?

Anything that keeps the pressure on the hot side of the system up in cold weather. The two common kinds switch condenser fans off, or back liquid up inside the condenser with a flooding valve.

Both make the condenser worse at its job, on purpose, so enough refrigerant still reaches the coil.

What does a crankcase heater do?

It keeps the compressor's oil warm while the compressor is off, so liquid refrigerant cannot settle in it in the cold.

Some makers require one on their condensing units. A failed one can leave a compressor that struggles to start after a cold night.

Is it normal for a condenser fan to be off in winter?

Yes, if the compressor is running and it is cold outside. Fan cycling controls switch condenser fans off on purpose to keep the pressure up.

At least one fan should still run whenever the compressor runs, and they should never all be cycled on one control.

Does an indoor walk-in need winter controls?

Usually not, as long as the room it sits in is heated.

A unit in an unheated garage, barn or back room sees the same cold as an outdoor one, and can need them.

When should winter controls be checked?

Before the cold season, or as soon as you see a box warm on a cold night. Book the technician before the next cold spell.

Give them your list of warm nights and outdoor lows. It is the quickest way to the fault.

See how your freezer copes with a cold night

Send us 30 days of readings from one walk-in, or let us put a sensor on it, and we will show you how it holds overnight and early in the morning. No purchase needed.

Talk with usTemperature monitoring for restaurants

Also see temperature monitoring for cold storage and warehouses.