Example walkthrough: SiteWise CMMS in action: rooftop HVAC preventive maintenance, the schedule and how to set it up
By Vimal Bhaya, Founder and Lead Systems Architect · Last reviewed 24 November 2026
This is a continuation of How to do it in SiteWise, a 10-part tutorial. You are on part 7 of 10.
Let's take a Carrier model 48TC rooftop unit and run PMs on it. Carrier lists a quarterly inspection in its manual (filters, belts, pulleys, bearing collars, the condenser coil and the condensate drain) and a check at the start of each cooling and heating season. In SiteWise that is three PMs on the unit: a quarterly PM and two yearly seasonal PMs, each title starting with the unit's name.
The manual splits the work into a quarterly inspection and seasonal checks
A rooftop unit (RTU) is a packaged heating and cooling unit that sits on the roof and feeds the building through ducts. Carrier's service and maintenance manual for its 48TC units, 3 to 6 tons, is a typical example. It lists these items, to be checked every month or two until you know what your own unit needs.
Turn off the main power switch to the unit before any service. The manual warns that electrical shock and rotating parts can cause injury.
| When | What the manual lists | Who does it |
|---|---|---|
| Every quarter, and 30 days after a new unit starts | Replace the return air filters; clean the outdoor hood inlet filters; check belt tension and condition; check pulley alignment; check the fan shaft bearing locking collars are tight; check the condenser coil is clean; check the condensate drain | Your own staff for the filters. A trained technician for the rest |
| Start of the cooling season | Condenser fan motor and compressor mounting bolts; condenser fan blade position; control box cleanliness and wiring; wire terminals; refrigerant charge; evaporator coil cleaning; evaporator blower motor amperage | A trained HVAC technician |
| Start of the heating season | Heat exchanger flue passages; gas burner condition; gas manifold pressure; heating temperature rise | A trained HVAC technician |
| Each season, with an economizer or outside air damper | Inlet filter condition; damper travel; gear and dampers free of debris and dirt | A trained technician |
The manual is clear on who does what. Only trained and qualified service people should repair or service the unit; anyone can replace the filters. Never open the refrigerant or gas side yourself.
Two numbers from the same manual help the person on the roof. Belt tension should be 6 lb at a 5/8 in (16 mm) deflection, measured at the middle of the belt span. And near the coast or in industrial areas, Carrier recommends rinsing the condenser coil with clean water every month.
Other makers' units follow the same pattern, but intervals and figures differ by model. Check your own unit's manual, and use its numbers where they differ.
The binder way is a checklist on a clipboard and a climb every quarter
- Print the checklist for each unit.
- Climb to the roof each quarter, and tick and sign.
- Bring it down and file it.
- Remember the seasonal checks in spring and fall, and book the contractor.
With five units that look alike on one roof, the ticks can end up on the wrong unit's sheet, and the seasonal checks depend on someone remembering the date.
The SiteWise way: three PMs on the unit
One SiteWise PM has one frequency, so the unit gets three. The full walk through the PM screens is in how to set up a preventive maintenance schedule. Here is the short version for a rooftop unit.
On the phone, as a manager
- Open Workorders, then Preventative, and tap +.
- Title it "RTU 3: quarterly inspection", and pick the roof as the Location and RTU 3 as the Asset.
- Under Add part, add the return air filters for this unit, and a spare belt. Under Add tool, add a belt tension gauge.
- On Trigger Settings, pick Regularly and set Work Order Due to every 3 months.
- Set the work order to open 7 days before the due date, or as long as your filter order takes, and tap Create PM Schedule.
- Add two more PMs on the same unit: "RTU 3: cooling season start" and "RTU 3: heating season start", each every 12 months, starting a few weeks before each season.
- Search "RTU 3" on Preventative. All three come up together.
- On the roof, the technician opens the work order and ticks each step, with photos of the coil and the drain.
* The phone screens show representative data, drawn from the app's design. Text in the real app is smaller, and a screen may differ slightly.
Put the manual's list on each PM as a procedure from the library: write the quarterly checklist once, and every rooftop unit's quarterly PM can use it. Tag each unit with a QR code so the technician opens the right one on the roof: see how to tag equipment with QR codes.
What you end up with is every unit's history, check by check
| The check | Clipboard checklist | SiteWise |
|---|---|---|
| Who else can see it | Whoever finds the sheet | The team, for every unit, on the phone or the web |
| Can you prove it was done | A signed sheet, if it was the right unit | The closed work order on that unit, with each step ticked and photos |
| Does anything chase it | Only the calendar | Each PM opens its work order before it is due, and the filters are reserved |
Seasonal PMs run on dates you choose
SiteWise runs each PM on the dates you set. Set the cooling season PM a few weeks before your summer starts and the heating season PM a few weeks before your first cold spell, and move them if your seasons shift.